PVC PRESSURE PIPE AS/NZS1477-1996 - SERIES 1
Nominal Size in mm |
Outside diameter minimum |
Outside diameter maximum |
15 |
21.2 |
21.5 |
20 |
26.6 |
26.9 |
25 |
33.4 |
33.7 |
32 |
42.1 |
42.4 |
40 |
48.1 |
48.4 |
50 |
60.2 |
60.5 |
65 |
75.2 |
75.5 |
80 |
88.7 |
89.1 |
100 |
114.1 |
114.5 |
125 |
140.0 |
140.4 |
150 |
160.0 |
160.5 |
200 |
225.0 |
225.6 |
225 |
250.0 |
250.7 |
250 |
280.0 |
280.8 |
300 |
315.0 |
315.9 |
350 |
355.0 |
356.0 |
375 |
400.0 |
401.0 |
400 |
450 |
451.0 |
450 |
500.0 |
501.0 |
500 |
560.0 |
561.0 |
575 |
630.0 |
631.0 |
PVC(Blue)PIPE AS/NZS1477-1996 SERIES 2.
COMPATIBLE WITH CAST IRON PIPE AS/NZS2544-1995
Nominal size in mm |
Outside diameter minimum |
Outside diameter maximum |
100 |
121.7 |
122.1 |
150 |
177.1 |
177.6 |
ASBESTOS CEMENT PIPE AS4139-1993
KNOWN AS FIBRELITE OR AC PIPE
Nominal size in mm |
Outside diameter +/- .08mm |
58 |
77.6 |
80 |
95.6 |
100 |
121.9 |
150 |
177.3 |
200 |
232.2 |
225 |
259.1 |
250 |
286.0 |
POLYETHYLENE PRESSURE PIPE
AS/NZS4130-1997
Nominal outside diameter in mm |
Mean Outside diameter minimum |
Mean Outside diameter maximum |
50 |
50.0 |
50.4 |
63 |
63.0 |
63.5 |
75 |
75.0 |
75.6 |
90 |
90.0 |
90.8 |
110 |
110.0 |
110.9 |
125 |
125.0 |
126.0 |
140 |
140.0 |
141.2 |
160 |
160.0 |
161.3 |
180 |
180.0 |
181.5 |
200 |
200.0 |
201.6 |
225 |
225.0 |
226.8 |
250 |
250.0 |
252.0 |
280 |
280.0 |
282.3 |
315 |
315.0 |
317.6 |
355 |
355.0 |
357.9 |
400 |
400.0 |
403.2 |
450 |
450.0 |
453.6 |
COMPARISON OF SDR & PRESSURE RATINGS
FOR PE80B AND PE100 MATERIALS
|
SDR41 |
SDR33 |
SDR26 |
SDR21 |
SDR17 |
SDR13.6 |
SDR11 |
SDR9 |
SDR7.4 |
PE80B |
PN3.2 |
PN4 |
- |
PN6.3 |
PN8 |
PN10 |
PN12.5 |
PN16 |
- |
PE100 |
PN4 |
- |
PN6.3 |
PN8 |
PN10 |
PN12.5 |
PN16 |
PN20 |
PN25 |
NOTE: SDR. Nominal ratio of outside diameter to wall thickness.
PE Classification. Long term rupture stress at 20o C (MPa multiplied by 10)
to which the minimum safety factor of 1.25 is applied in orde
to obtain the 20o C design hoop stress.
PN. Pressure rating at 20o C (MPa multiplied by 10).